{}

我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
Modbus register reading 32768 or -32768

Issue
Modbus register returns value of 32768 or -32768 when using modbus tester to read holding registers

Product Line
PowerLogic Meters
Micrologic Trip Units

Environment
ION Setup
Tester
Modbus Register Readings

Cause
There are two situations that will cause a register in a PowerLogic Circuit Monitor, Power Meter, or other PowerLogic device to contain a value of -32768.

  1. When there is no input (voltage or current) to calculate or measure a metered value.
  2. When the register value is non-applicable for the mode of the meter.
  3. When you are reading the wrong unit ID of an Ethernet device, i.e., unit ID 1 instead of 255 on a PM5560

Example: The frequency register in a CM4250 will read -32768 when no voltage or current is present.

Note: System Manager Software (SMS) will indicate N/A when a register value contains the value -32768 and Power Monitoring Expert (PME) 8.1 will show 0.

Resolution
In many cases a power cycle to the meter or micrologic trip unit will resolve this issue.
If a power cycle does not resolve this issue, please contact your local Schneider Technical support representatives for further troubleshooting or RMA

施耐德電機Taiwan

Modbus register reading 32768 or -32768

Issue
Modbus register returns value of 32768 or -32768 when using modbus tester to read holding registers

Product Line
PowerLogic Meters
Micrologic Trip Units

Environment
ION Setup
Tester
Modbus Register Readings

Cause
There are two situations that will cause a register in a PowerLogic Circuit Monitor, Power Meter, or other PowerLogic device to contain a value of -32768.

  1. When there is no input (voltage or current) to calculate or measure a metered value.
  2. When the register value is non-applicable for the mode of the meter.
  3. When you are reading the wrong unit ID of an Ethernet device, i.e., unit ID 1 instead of 255 on a PM5560

Example: The frequency register in a CM4250 will read -32768 when no voltage or current is present.

Note: System Manager Software (SMS) will indicate N/A when a register value contains the value -32768 and Power Monitoring Expert (PME) 8.1 will show 0.

Resolution
In many cases a power cycle to the meter or micrologic trip unit will resolve this issue.
If a power cycle does not resolve this issue, please contact your local Schneider Technical support representatives for further troubleshooting or RMA

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
探索更多
系列:
探索更多
系列:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.