What are the various generations of Smart-UPS Products?

Issue:

What are the various generations of single phase Smart-UPS Products?

Product Line:

Smart-UPS

Environment:

All models, All Serial Numbers

Cause:

With over 20 million units sold, many customers have a variety of Smart-UPS products in use. Over the years APC has steadily improved the product line. This document highlights the generations that are likely to still be used in production environments. Please note that this is a high level overview, and not all features are detailed. For more detailed specifications, or to find software and accessory compatibility, please refer to the apc.com product page for your specific UPS.

Resolution:

Current Products:

These products are currently in production and available for purchase.
We will identify the different generations by their part number prefix.

SMT1000
"SMT" (IE: SMT1000)
  • High efficiency “green” mode
  • Next generation Line Interactive Smart-UPS products
  • 750VA - 3kVA
  • Pure Sinewave
  • Line Interactive topology
  • Fully interactive LCD display
  • Both rackmount and tower versions available
  • Standard Run battery only
  • Switched receptacle group
  • Enhanced battery management
  • Flash upgrade able firmware
  • Serial or USB Communications (RJ-45 Serial Port on UPS)
  • Microlink Protocol
  • Smart-Slot for installation of APC Accessory Cards



SMX1000

"SMX" (IE: SMX1000)
  • Next generation Line Interactive Smart-UPS products
  • 750VA - 3kVA
  • Pure Sinewave
  • Line Interactive topology
  • Fully interactive LCD display
  • All units Rack / Tower convertible
  • All units have the option of intelligent extended run battery packs
  • High efficiency “green” mode
  • Switched receptacle groups
  • Enhanced battery management
  • Voltage adaptability  ( 2kVA & up only )
  • Higher power factor than comparable "SMT" units
  • Flash upgrade able firmware
  • Serial or USB Communications (RJ-45 Serial Port on UPS)
  • Microlink Protocol
  • Smart-Slot for installation of APC Accessory Cards




SMC1000

"SMC" (IE: SMC1000)
  • Next generation Entry-Level Line Interactive Smart-UPS products
  • 1kVA - 1.5kVA
  • Pure Sinewave
  • Line Interactive topology
  • Simplified LCD display
  • Both rackmount and tower versions available
  • Standard Run battery only
  • High efficiency “green” mode
  • Flash upgrade able firmware
  • USB Communications (Serial Cable available as an option)  (RJ-45 Serial Port on UPS)
  • No Smart-Slot
  • Microlink Protocol
  • Designed for entry level server and Small Office / Home Office applications



SUM1500RMXL2U

"SUM" (IE: SUM1500RMXL2U)
  • Modular Line Interactive Smart-UPS (Similar to 4th generation "SUA" units)
  • 1.5kVA - 3kVA
  • Pure Sinewave
  • Line Interactive topology
  • LED Display
  • All units are Rack/Tower convertible
  • Unit is comprised of a Chassis, a Battery Module, and a Power Module
  • Battery and Power Modules are hot-swapable
  • Extended Run (XL) battery options
  • Automatic Voltage Regulation with Double Boost
  • Intelligent Battery Management
  • Serial or USB Communications (You can only use one at a time)  (RJ-45 Serial Port on UPS)
  • User controllable outlet groups
  • Bypass capability
  • UPS-Link Communications Protocol
  • Smart-Slot for installation of APC Accessory Card (Ships populated with a Network Management Card)


SURT10000XLT

"SURT" (IE: SURT10000XLT) 1st generation of Smart-UPS Online products
  • 1kVA - 20kVA
  • Double Conversion Online Topology with zero transfer time
  • Bypass capability
  • LED Display
  • Rack / Tower or Rack / Stack convertible
  • All units have Extended Run (XL) battery options
  • Intelligent Battery Management
  • Serial communications  (RJ-45 Serial Port on "SURTD" Models, DB-9 on all others)
  • UPS-Link Communications Protocol (Microlink Protocol on "SURTD" models)
  • Smart-Slot for installation of APC Accessory Cards


"SRT" (IE: SRT10KXLT) 2nd generation of Smart-UPS Online products
  • 3kVA - 10kVA
  • Double Conversion Online Topology with zero transfer time
  • Bypass capability
  • LCD Display
  • Rack / Tower or Rack / Stack convertible
  • All units have Extended Run (XL) battery options
  • Intelligent Battery Management
  • Serial and USB communications
  • Microlink Communication Protocol
  • Smart-Slot for installation of APC Accessory Cards
  • 5Kva and larger include embedded Network Management Cards

Legacy Products:

These products are mostly discontinued, or are only sold in limited regions or for specific applications.
We will identify the different generations by their part number prefix.



SU700NET

"SU" (IE: SU700NET)
  • 3rd Generation of Line Interactive Smart-UPS products
  • 700VA - 5kVA
  • Pure Sinewave
  • Line Interactive topology
  • Beige colors cases
  • LED Display
  • Both rackmount and tower versions available
  • Standard or Extended Run (XL) battery options
  • Automatic Voltage Regulation
  • Intelligent Battery Management
  • Serial Communications (DB-9 Serial Port)
  • UPS-Link Communications Protocol
  • Smart-Slot for installation of APC Accessory Cards




"SUA" (IE: SUA750)
  • 4th Generation of Line Interactive Smart-UPS products
  • 700VA - 5kVA
  • Pure Sinewave
  • Line Interactive topology
  • Black colored cases
  • LED Display
  • Both rackmount and tower versions available
  • Standard or Extended Run (XL) battery options
  • Automatic Voltage Regulation with Double Boost
  • Intelligent Battery Management
  • Serial (DB-9 Serial Port) or USB Communications (You can only use one at a time)
  • UPS-Link Communications Protocol
  • Smart-Slot for installation of APC Accessory Cards



"SC" (IE: SC620)
  • Low cost Smart-UPS for Networking
  • 420VA - 1.5kVA
  • Step Approximated Sinewave
  • Line Interactive topology
  • Black colored cases
  • LED Display
  • Tower and Rack/Tower convertible units
  • Standard Run battery only
  • Automatic Voltage Regulation
  • Serial or Serial & USB depending on model (DB-9 Serial Port)
  • UPS-Link Communications Protocol
  • No Smart-Slot
  • For use with low power networking applications

施耐德電機Taiwan

What are the various generations of Smart-UPS Products?

Issue:

What are the various generations of single phase Smart-UPS Products?

Product Line:

Smart-UPS

Environment:

All models, All Serial Numbers

Cause:

With over 20 million units sold, many customers have a variety of Smart-UPS products in use. Over the years APC has steadily improved the product line. This document highlights the generations that are likely to still be used in production environments. Please note that this is a high level overview, and not all features are detailed. For more detailed specifications, or to find software and accessory compatibility, please refer to the apc.com product page for your specific UPS.

Resolution:
 

Current Products:

These products are currently in production and available for purchase.
We will identify the different generations by their part number prefix.

SMT1000
"SMT" (IE: SMT1000)
  • High efficiency “green” mode
  • Next generation Line Interactive Smart-UPS products
  • 750VA - 3kVA
  • Pure Sinewave
  • Line Interactive topology
  • Fully interactive LCD display
  • Both rackmount and tower versions available
  • Standard Run battery only
  • Switched receptacle group 
  • Enhanced battery management 
  • Flash upgrade able firmware
  • Serial or USB Communications (RJ-45 Serial Port on UPS)
  • Microlink Protocol 
  • Smart-Slot for installation of APC Accessory Cards
     



SMX1000

"SMX" (IE: SMX1000)
  • Next generation Line Interactive Smart-UPS products
  • 750VA - 3kVA
  • Pure Sinewave
  • Line Interactive topology
  • Fully interactive LCD display
  • All units Rack / Tower convertible
  • All units have the option of intelligent extended run battery packs
  • High efficiency “green” mode
  • Switched receptacle groups 
  • Enhanced battery management 
  • Voltage adaptability  ( 2kVA & up only )
  • Higher power factor than comparable "SMT" units
  • Flash upgrade able firmware
  • Serial or USB Communications (RJ-45 Serial Port on UPS)
  • Microlink Protocol 
  • Smart-Slot for installation of APC Accessory Cards




SMC1000 

"SMC" (IE: SMC1000)
  • Next generation Entry-Level Line Interactive Smart-UPS products
  • 1kVA - 1.5kVA
  • Pure Sinewave
  • Line Interactive topology
  • Simplified LCD display
  • Both rackmount and tower versions available
  • Standard Run battery only
  • High efficiency “green” mode
  • Flash upgrade able firmware
  • USB Communications (Serial Cable available as an option)  (RJ-45 Serial Port on UPS)
  • No Smart-Slot
  • Microlink Protocol 
  • Designed for entry level server and Small Office / Home Office applications



SUM1500RMXL2U

"SUM" (IE: SUM1500RMXL2U)
  • Modular Line Interactive Smart-UPS (Similar to 4th generation "SUA" units)
  • 1.5kVA - 3kVA
  • Pure Sinewave
  • Line Interactive topology
  • LED Display
  • All units are Rack/Tower convertible
  • Unit is comprised of a Chassis, a Battery Module, and a Power Module
  • Battery and Power Modules are hot-swapable
  • Extended Run (XL) battery options 
  • Automatic Voltage Regulation with Double Boost
  • Intelligent Battery Management 
  • Serial or USB Communications (You can only use one at a time)  (RJ-45 Serial Port on UPS)
  • User controllable outlet groups
  • Bypass capability
  • UPS-Link Communications Protocol
  • Smart-Slot for installation of APC Accessory Card (Ships populated with a Network Management Card)


 
SURT10000XLT

"SURT" (IE: SURT10000XLT) 1st generation of Smart-UPS Online products
  • 1kVA - 20kVA
  • Double Conversion Online Topology with zero transfer time
  • Bypass capability
  • LED Display
  • Rack / Tower or Rack / Stack convertible
  • All units have Extended Run (XL) battery options 
  • Intelligent Battery Management
  • Serial communications  (RJ-45 Serial Port on "SURTD" Models, DB-9 on all others)
  • UPS-Link Communications Protocol (Microlink Protocol on "SURTD" models)
  • Smart-Slot for installation of APC Accessory Cards


"SRT" (IE: SRT10KXLT) 2nd generation of Smart-UPS Online products
  • 3kVA - 10kVA
  • Double Conversion Online Topology with zero transfer time
  • Bypass capability
  • LCD Display
  • Rack / Tower or Rack / Stack convertible
  • All units have Extended Run (XL) battery options 
  • Intelligent Battery Management
  • Serial and USB communications
  • Microlink Communication Protocol
  • Smart-Slot for installation of APC Accessory Cards
  • 5Kva and larger include embedded Network Management Cards
 

Legacy Products:

These products are mostly discontinued, or are only sold in limited regions or for specific applications.
We will identify the different generations by their part number prefix.



SU700NET

"SU" (IE: SU700NET)
  • 3rd Generation of Line Interactive Smart-UPS products
  • 700VA - 5kVA
  • Pure Sinewave
  • Line Interactive topology
  • Beige colors cases
  • LED Display
  • Both rackmount and tower versions available
  • Standard or Extended Run (XL) battery options 
  • Automatic Voltage Regulation
  • Intelligent Battery Management
  • Serial Communications (DB-9 Serial Port)
  • UPS-Link Communications Protocol
  • Smart-Slot for installation of APC Accessory Cards




"SUA" (IE: SUA750)
  • 4th Generation of Line Interactive Smart-UPS products
  • 700VA - 5kVA
  • Pure Sinewave
  • Line Interactive topology
  • Black colored cases
  • LED Display
  • Both rackmount and tower versions available
  • Standard or Extended Run (XL) battery options 
  • Automatic Voltage Regulation with Double Boost
  • Intelligent Battery Management 
  • Serial (DB-9 Serial Port) or USB Communications (You can only use one at a time)
  • UPS-Link Communications Protocol
  • Smart-Slot for installation of APC Accessory Cards



"SC" (IE: SC620)
  • Low cost Smart-UPS for Networking
  • 420VA - 1.5kVA
  • Step Approximated Sinewave
  • Line Interactive topology
  • Black colored cases
  • LED Display
  • Tower and Rack/Tower convertible units
  • Standard Run battery only
  • Automatic Voltage Regulation
  • Serial or Serial & USB depending on model (DB-9 Serial Port)
  • UPS-Link Communications Protocol
  • No Smart-Slot
  • For use with low power networking applications

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
探索更多
系列:
探索更多
系列:

需要協助?

  • 從這裡開始!

    現在就找尋答案。自行搜尋解決方案,或與我們的專家聯絡。

  • 聯絡客服

    聯繫我們的客戶服務團隊以獲得更多資訊、技術支援、投訴協助等。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 瀏覽 FAQ

    瀏覽主題相關常見問題 (FAQ),藉此取得您所需要的答案。

  • 聯絡業務

    歡迎您線上提問,將有專家與您聯絡。

我願意透過電子通訊方式(如電子郵件)從施耐德電機及其附屬公司接收新聞和商業資訊,我也同意他們收集這些電子郵件的開啟和點擊資訊(使用隱藏式追蹤像素),以衡量溝通效益並優化這些資訊。如您需更多詳細資訊,請參閱施耐德電機的 隱私權政策

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.