Can the ATV312 Drive switch from local keypad control to remote terminal control by pressing and holding the mode button?

Article available in these languages: 西班牙文

Issue:
ATV312, local mode to remote mode.

Product:
ATV312  Altivar 312

Environment:
All

Cause:
Programming was changed.

Resolution:
The drive can be changed from remote (Terminal) mode to local (Keypad) mode by pressing and holding the mode for 3 seconds.
However, when returning to remote from local requires the drive to be reset to factory defaults using the FCS parameter in the drC menu.
Consult the ATV312 Programming manual for details.