搜尋常見問題
Can the ATV312 Drive switch from local keypad control to remote terminal control by pressing and holding the mode button?
Issue:
ATV312, local mode to remote mode.
Product:
ATV312 Altivar 312
Environment:
All
Cause:
Programming was changed.
Resolution:
The drive can be changed from remote (Terminal) mode to local (Keypad) mode by pressing and holding the mode for 3 seconds.
However, when returning to remote from local requires the drive to be reset to factory defaults using the FCS parameter in the drC menu.
Consult the ATV312 Programming manual for details.
https://www.se.com/ww/en/download/document/BBV46385/
ATV312, local mode to remote mode.
Product:
ATV312 Altivar 312
Environment:
All
Cause:
Programming was changed.
Resolution:
The drive can be changed from remote (Terminal) mode to local (Keypad) mode by pressing and holding the mode for 3 seconds.
However, when returning to remote from local requires the drive to be reset to factory defaults using the FCS parameter in the drC menu.
Consult the ATV312 Programming manual for details.
https://www.se.com/ww/en/download/document/BBV46385/
發佈於:施耐德電機Taiwan
探索更多
系列:
探索更多
系列: