{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站

搜尋常見問題

What can cause a GrdF ground fault on the ATS22 soft starter?

Issue:
The ATS22 softstart unit trips on Ground Fault (GrdF).

Product Line:
ATS22

Environment:
All

Cause:
Tripping the unit

Resolution:
This is a Ground Leakage current detected fault.
Check the motor and wires insulation.
Check for proper installation and Grounding.
Check the settings Grdd, Grdt parameters in PrO menu.

施耐德電機Taiwan

探索更多
系列:
Altistart 22
探索更多
系列:
Altistart 22