How can we control constant pressure in water pipe line using ATV212 drive?
You should use PID control in ATV21 / ATV212 drive to increase or decrease the speed automatically to maintain the set pressure in water pipe line.
It is important to have the pressure set point and pressure feedback for PID control in VFD.

1. Pressure set point - This is the pressure reference provided to the VFD through Analog input AI1. The analog input can be from drive keypad, 0 - 10VDC though potentiometer or 4 to 20 mA from PLC etc...
If you operate the VFD form the keypad(local mode), you can adjust the set point through up and down buttons given in the drive.
If you want to use external set point, the set point reference (0 - 10 VDC) should be connected between CC and VIB terminals.
a)you can connect a potentiometer between terminals PP(10VDC), VIB & CC to vary the reference from 0 to 10VDC.
b)If you give the reference form PLC you can connect the reference between VIB & CC directly.

2. Pressure feedback - The feedback should be connected between VIA & CC in VFD terminals. It is necessary to use analog pressure transducer(0-10V or 4-20mA or 0-20mA) give feedback to drive.

Please refer the attached technical resolution document for the wiring and setting of PID Control using ATV212 drive.

施耐德電機Taiwan

附件
ATV212 PID-with input, output, wiring diagram and Drive programming.pdf [307.09 KB]
How can we control constant pressure in water pipe line using ATV212 drive?
You should use PID control in ATV21 / ATV212 drive to increase or decrease the speed automatically to maintain the set pressure in water pipe line.
It is important to have the pressure set point and pressure feedback for PID control in VFD. 

1. Pressure set point - This is the pressure reference provided to the VFD through Analog input AI1. The analog input can be from drive keypad, 0 - 10VDC though potentiometer or 4 to 20 mA from PLC etc...
If you operate the VFD form the keypad(local mode), you can adjust the set point through up and down buttons given in the drive.
If you want to use external set point, the set point reference (0 - 10 VDC) should be connected between CC and VIB terminals. 
a)you can connect a potentiometer between terminals PP(10VDC), VIB & CC to vary the reference from 0 to 10VDC. 
b)If you give the reference form PLC you can connect the reference between VIB & CC directly. 

2. Pressure feedback - The feedback should be connected between VIA & CC in VFD terminals. It is necessary to use analog pressure transducer(0-10V or 4-20mA or 0-20mA) give feedback to drive. 

Please refer the attached technical resolution document for the wiring and setting of PID Control using ATV212 drive.

施耐德電機Taiwan

附件
ATV212 PID-with input, output, wiring diagram and Drive programming.pdf [307.09 KB]
探索更多
系列:
探索更多
系列:
探索更多
系列:
探索更多
系列:

需要協助?

  • 從這裡開始!

    現在就找尋答案。自行搜尋解決方案,或與我們的專家聯絡。

  • 聯絡客服

    聯繫我們的客戶服務團隊以獲得更多資訊、技術支援、投訴協助等。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 瀏覽 FAQ

    瀏覽主題相關常見問題 (FAQ),藉此取得您所需要的答案。

  • 聯絡業務

    歡迎您線上提問,將有專家與您聯絡。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.