搜尋常見問題
What is the difference between the AS-MBKT-085 and the AS-MBKT-185 Modbus Plus connectors?
Title
Difference between the AS-MBKT-085 and the AS-MBKT-185
Issue
Modbus Plus Connector difference
Product Line
Modbus Plus
Resolution
The AS-MBKT-185 connector has an integrated 120 ohm terminating resistor. These connectors can only be installed on the ends of the Modbus Plus network. The AS-MBKT-085 connector does not have an internal terminating resistor. These connectors can be installed on any Modbus Plus node in between the end nodes. The AS-MBKT -085 connector is a dark gray color whereas the AS-MBKT -185 connector is a light gray color..
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Difference between the AS-MBKT-085 and the AS-MBKT-185
Issue
Modbus Plus Connector difference
Product Line
Modbus Plus
Resolution
The AS-MBKT-185 connector has an integrated 120 ohm terminating resistor. These connectors can only be installed on the ends of the Modbus Plus network. The AS-MBKT-085 connector does not have an internal terminating resistor. These connectors can be installed on any Modbus Plus node in between the end nodes. The AS-MBKT -085 connector is a dark gray color whereas the AS-MBKT -185 connector is a light gray color..
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
發佈於:施耐德電機Taiwan
探索更多
系列:
探索更多
系列: