Why do we get Array size exceeded error for variable tag in Vijeo Citect 7.5?
From Vijeo Citect 7.1 onwards compiler checks for the maximum length of an array and if it exceeds 256 bytes or 128 words, an “Array size exceeded” error  is generated.
Solution is to reduce the array size to 128.