{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
Why the island node configuration of STB is blank when it is opened from Unity Pro NOE I/O scanning STB DTM tab through zef ?
The zef file doesn't include the STB configuration information inside of NOE I/O scanning field ,so the blank page will be opened if you active the STB DTM through I/O scanning.
There are two solutions could be used
1> Customer could save the old application as sta format and reopen it in newer Unity Pro ,all the STB information are included
2>copy the previous STB configuration files (*.isl ) to current unity import/export folder ,open the zef file and all STB info could be visible.

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: