With HMI as speed reference, can the the display be changed to show something else on ATV630/930 Drives?

Article available in these languages: 西班牙文

Issue:
ATV630/930 display configuration with local speed reference

Product line:
ATV6730, Altivar Process

Environment:
all

Cause:
Display defaults to Frequency Reference.

Resolution:
The main display cannot be changed when using the HMI as the speed reference.  It will always show the Reference Frequency applied by the HMI.  The display top bar can be customized to show other information. Go to My Preferences > Customization > Param Bar Select and select desired items to monitor.