How to display individual Web applications without banners or tabs in Power Monitoring Expert
Issue
User would like to display a specific web application in Power Monitoring Expert (PME)

Product
Power Monitoring Expert 8.x, PME 9.x

Environment
Web browser

Resolution

The tables below show the url to use to access the individual web applications. Replace [servername] with the name or IP address of the PME server hosting the web applications.

PME 8.x:
Dashboards http://[servername]/Dashboards/
Default Network Diagram http://[servername]/ion/
Tables http://[servername]/web/application/Tables
Trends http://[servername]/trends
Alarms http://[servername]/web/application/Alarms
Reports http://[servername]/reporter/

PME 9.x:
Dashboards https://[servername]/Dashboards/
Default Network Diagram https://[servername]/ion/
Diagrams https://[servername]/diagrams/
Trends https://[servername]/trends
Alarms https://[servername]/Alarms
Reports https://[servername]/reporter/