我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Video: How are the basic parameters set up in ATV320 Drive?

Article available in these languages: Czech, 西班牙文, 芬蘭文, 韓文

Issue:
Parameters to set up in a ATV320 Drive.

Product Line:
Altivar 320

Environment:
All ATV320 drives

Cause:​
Basic programming

Resolution:
CONF>FULL>SIM
tFr= Max frequency
ItH= Motor thermal Current (motor FLA)
ACC= ramp up time
dEC= ramp down time
LSP= Low speed
HSP= High speed

CONF>FULL>drC
bFr= Base motor frequency 60hz

CONF>FULL>drC>ASY
nPr= HP of the motor
UnS= Rated motor voltage
nCr= Rated motor current (Motor FLA)
FrS= Rated motor frequency
nSP= Rated motor speed (RPM)

CONF>FULL>SET
CLI= current limit (maximum current, must be greater than FLA, up to 150% of FLA)

NOTE: Make sure to use the information on your motor's nameplate for programming. 

Please refer to ATV320 Programming Manual, document # NVE41295 for additional details.

 

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 從這裡開始!

    現在就找尋答案。自行搜尋解決方案,或與我們的專家聯絡。

  • 聯絡客服

    聯繫我們的客戶服務團隊以獲得更多資訊、技術支援、投訴協助等。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 瀏覽 FAQ

    瀏覽主題相關常見問題 (FAQ),藉此取得您所需要的答案。

  • 聯絡業務

    歡迎您線上提問,將有專家與您聯絡。

我願意透過電子通訊方式(如電子郵件)從施耐德電機及其附屬公司接收新聞和商業資訊,我也同意他們收集這些電子郵件的開啟和點擊資訊(使用隱藏式追蹤像素),以衡量溝通效益並優化這些資訊。如您需更多詳細資訊,請參閱施耐德電機的 隱私權政策

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.