{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
What happens to the data points rtH, rtHI, and ptH on the ATV61 and ATV71 drives when it exceeds its maximum value of 65536 Hours?

Article available in these languages: 西班牙文

Issue:
Data points rtH, rtHI,  and ptH on the ATV61 and ATV71 drives exceed its maximum value of 65536 Hours

Product Line:
Altivar ATV61 and ATV71

Environment:
All

Cause:
Need to Reset Run time parameters after 7 years

Resolution:
When RTH, RTHI, PTH or PET value reaches 65535 (65535 hours = 2730 days = 7 years), the counter stays blocked at this value.
Also, It is impossible to reset PTH parameter.

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: