What happens to the data points rtH, rtHI, and ptH on the ATV61 and ATV71 drives when it exceeds its maximum value of 65536 Hours?

Article available in these languages: 西班牙文

Issue:
Data points rtH, rtHI,  and ptH on the ATV61 and ATV71 drives exceed its maximum value of 65536 Hours

Product Line:
Altivar ATV61 and ATV71

Environment:
All

Cause:
Need to Reset Run time parameters after 7 years

Resolution:
When RTH, RTHI, PTH or PET value reaches 65535 (65535 hours = 2730 days = 7 years), the counter stays blocked at this value.
Also, It is impossible to reset PTH parameter.