You will need to assign a variable to %MDx Location and Read at least 2 registers where the Float is located on your Remote Device. Move the Registers into %MWx*2 and %MWx*2+1.
See Attached project archive file for example. The following video demonstrates this procedure:
See Attached project archive file for example. The following video demonstrates this procedure: