How to derate ATV630/650 drives for high elevation installation?
Issue:
Deration for ATV630/650 drives for high elevation installation

Product Line:
Altivar Process 630/650

Resolution:
0...1000m / 0...3300ft without derating
1,000...4,800m / 3,300...15,700ft with derating
See attachment, excerpt from the Installation manual, document number EAV64301.