Can I use only one push button without password to reset the latches?
Yes, by using one of the F buttons. In function buttons menu, define F1 “Selected control” F1 and give a pulse time, e.g. 1s. In “Release latches” menu define “DI to release latches” as F1. Alternatively, you can use F2.