Is it possible to monitor status of Extension card digital and analog signals via web server on Altivar ATV630, ATV930, ATV340...E?
Yes, it is possible. After login to the web server, in the section displaying - I/O status all the inputs are visible. See printscreen.
Analog signals, can be monitored also in the dashboard menu. To be able to see them in the dashboard, it is necessary to create a new table with required variables. See the print screen with added AI4 and AI5 analog signals. Then the table can be added to dashboard as a widget.

施耐德電機Taiwan

附件
WEb_Server_ATV630_IOstatus.jpg [401.95 KB]
WEb_Server_ATV630_Create new table.jpg [167.55 KB]
WEb_Server_ATV630_Add table to dashboard.jpg [359.97 KB]
Is it possible to monitor status of Extension card digital and analog signals via web server on Altivar ATV630, ATV930, ATV340...E?
Yes, it is possible. After login to the web server, in the section displaying - I/O status all the inputs are visible. See printscreen.
Analog signals, can be monitored also in the dashboard menu. To be able to see them in the dashboard, it is necessary to create a new table with required variables. See the print screen with added AI4 and AI5 analog signals. Then the table can be added to dashboard as a widget.

施耐德電機Taiwan

附件
WEb_Server_ATV630_IOstatus.jpg [401.95 KB]
WEb_Server_ATV630_Create new table.jpg [167.55 KB]
WEb_Server_ATV630_Add table to dashboard.jpg [359.97 KB]
探索更多
系列:
探索更多
系列:
探索更多
系列:
探索更多
系列:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.