When powering multiple ATV930 drives straight to the DC bus with a common DC power supply, what parameters need to be adjusted?
Issue:
Parameters to adjust when powering multiple ATV930 drives straight to the DC bus with a common DC power supply.

Product Line:
Altivar 930

Environment:
All

Cause:
Powering ATV930's with a single common DC power supply

Resolution:
1. Set your Access Level to Expert:
- [My Preferences] ->  [Access Level] -> [Expert]

2. Set DC Bus Source Type to Supply Unit REC:
- [Complete settings] -> [Generic functions] ->[dbS] ->[dCbS] ->[Supply Unit REC]