搜尋常見問題
Video: Where can I find the Skip frequency parameter settings in the ATV630 process drive?
Issue:
Programming and understand skip frequency function of ATV630
Product Line:
ATV600
Environment:
All serial numbers
Cause:
Prevent prolonged operation within an adjustable range. Minimize noise at (x) frequency.
Resolution:
Jump frequency parameters can be located in Main Menu [Complete settings] -> [Generic Functions] -> [Jump frequency]
3 possible skip frequencies can be added at a time.
Skip frequency hysteresis is the frequency value range skipped.
For example, we have skip frequency value at 30 hz with hysteresis of 3hz. This means that the frequency range 27-33 will be skipped on ramp.
Programming and understand skip frequency function of ATV630
Product Line:
ATV600
Environment:
All serial numbers
Cause:
Prevent prolonged operation within an adjustable range. Minimize noise at (x) frequency.
Resolution:
Jump frequency parameters can be located in Main Menu [Complete settings] -> [Generic Functions] -> [Jump frequency]
3 possible skip frequencies can be added at a time.
Skip frequency hysteresis is the frequency value range skipped.
For example, we have skip frequency value at 30 hz with hysteresis of 3hz. This means that the frequency range 27-33 will be skipped on ramp.
發佈於:施耐德電機Taiwan
探索更多
系列:
探索更多
系列: