What is an internal serial link fault (INF3) on an ATV320 drive?
Issue:
Internal serial link fault (INF3) meaning on an ATV320.

Product Line:
Altivar 320

Environment:
All

Cause:
Communication interruption between internal cards of VFD

Resolution:
Check internal connections.
If there is an option card, remove and re install.
Power cycle the VFD.
Factory reset if needed.