搜尋常見問題
How to manage the redundancy channel of SDI module in M580 safety PLC?
To use the S_EQUIVALENT function block to convert two equivalent BOOL inputs – both inputs either normally closed (NC) or normally open (NO) – to a single BOOL output with discrepancy time monitoring.