{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
What sinus filters do we offer for LHP ATV61 drives at 690V?
Sinus filter offer for 690V ATV61 is limited and so available for drives 110kW and above (ATV61HC11Y...C80Y)
For LHP drives ATV61...Y  (HD15Y..HD90Y) it is possible to use 2 motor chokes in series and achieve max 300m unshielded cable length.

Or alternative solution  is to use
ATV630.
ATV630...Y6 drives allows to use sinus filter for 690V from 2.2KW and above and achieve max 500m unshielded motor cable cable. See extract attached.

施耐德電機Taiwan

附件
Extracted pages from ATV600 Catalog 2018-05 _DIA2ED2140502EN.pdf [282.05 KB]
探索更多
系列:
可能有幫助的文章
探索更多
系列: