{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
How do I configure a NOC301/311 for no gateway when the DTM will not accept a gateway address of 0.0.0.0.
Issue
How do I configure a BMENOC0301 or BMENOC0311 for 'no gateway' when the DTM will not accept a gateway address of 0.0.0.0?


Product Line
BMENOC0301
BMENOC0311

Environment
Unity, Control Expert

Resolution
The user can enter the BMENOC IP address as the gateway IP which will essentially direct any gateway traffic to itself which will would be as if he had no gateway configured.  This is a common practice to avoid entering 0.0.0.0 as a configured gateway address.

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: