搜尋常見問題
HEP meter Log Export module unsent data after setup change
Issue
After making a change to the Log Export, any unsent log data is never sent from the meter.
Product
High End Platform meters (HEP)
ION 9000
PM 8000
ION 7400
Environment
SMTP
Cause
When the module has a setup change the module is initialized with the new settings. The process of the initializing will set the log export module to the end of the data recorder. Any attempt to pulse the Log Export module to retrieve the old data will result in message in the meter's eventlog no new records found.
Resolutions
Intended behavior of meter. Be sure all data from desired Data Recorder is sent before making a change to the Log Export module.
After making a change to the Log Export, any unsent log data is never sent from the meter.
Product
High End Platform meters (HEP)
ION 9000
PM 8000
ION 7400
Environment
SMTP
Cause
When the module has a setup change the module is initialized with the new settings. The process of the initializing will set the log export module to the end of the data recorder. Any attempt to pulse the Log Export module to retrieve the old data will result in message in the meter's eventlog no new records found.
Resolutions
Intended behavior of meter. Be sure all data from desired Data Recorder is sent before making a change to the Log Export module.
發佈於:施耐德電機Taiwan
探索更多
系列:
探索更多
系列: