{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
HEP meter with V2.2 Firmware CID files occasionally fail to parse correctly on first attempt
Issue
Uploading a valid CID file to the meter via sFTP will be flanged by the HEP as an invalid CID file in the IEC 61850 log.

Product
ION9000, ION7400, PM8000 with V2.2 Firmware

Environment
SFTP

Cause
Depending on the sFTP client, when transferring a file, a temporary file can be created that is renamed after the upload is complete. This may result in the meter trying to parse the file before the upload is complete.

Resolution
Upload the file again and verify the IEC 61850 log shows that IEC 61850 is running.

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: