Issue:
PTC probe wiring on ATV320 drive.
Product Line:
Altivar Machines, Altivar 320
Environment:
All models and serial numbers
Cause:
N/A
Resolution:
DI6 can be used as PTC (Positive Temperature Coefficient) using SW2 switch (see page 89 of manual).
Trip threshold: 3 kΩ, reset threshold: 1.8 kΩ
Short-circuit detection threshold < 50 Ω

Wire the PTC to DI6 and COM.
PTC probe wiring on ATV320 drive.
Product Line:
Altivar Machines, Altivar 320
Environment:
All models and serial numbers
Cause:
N/A
Resolution:
DI6 can be used as PTC (Positive Temperature Coefficient) using SW2 switch (see page 89 of manual).
Trip threshold: 3 kΩ, reset threshold: 1.8 kΩ
Short-circuit detection threshold < 50 Ω
Wire the PTC to DI6 and COM.
發佈於:施耐德電機Taiwan

