{}
搜尋常見問題
How to configure Event Watcher to trigger on Sag/Swell events only
Product Line
Power Monitoring Expert

Environment
Event Watcher

Resolution
Event Watcher must be configured to use a template the only references Sag/Swell Events.

To create the template follow the steps below:
  1. Open Event Watcher by going to Management Console, select Tools >> Reporting Configuration >> Event Watcher Manager
  2. Select the Templates tab
  3. Click New
  4. Give the alarm a name such as PQ Events - Sag/Swell
  5. If desired, give the alarm a description
  6. Choose 'Select From Event Log'
  7. Select Sag/Swell {0.EN_US}|1 Disturbance Start SS1 DistState Disturbance
  1. Press OK and then apply to save the template

Configure Event watcher to use the Sag/Swell template by using the following steps.
  1. Inside of Event Watcher choose the Event Watchers tab.
  2. Select New in the top right
  3. Give the alarm a name
  4. Select the Sag/Swell template created above
  5. If desired, give the alarm a description
  6. Select the device(s) that the alarm will apply to
  1. Press OK
For steps on how to create a report subscription using this event trigger see FA300069.

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: