搜尋常見問題
PME2020/ Energy Expert 3.0 How to enable the Multi-Use Token Functionality
Section 1 – Product /System/Environment information
EcoStruxure™ Energy Expert 3.0 Solution Guide
Energy Expert 3.0
Power Monitoring Expert 2020
_____________________________________________________________________________________
Section 2 – Issue
There is a mistake in the documentation EcoStruxure™ Energy Expert 3.0 Solution Guide on page 183. ( It has been observed that row is duplicated instead of updated)
The SQL script does not enable the multi-use token
EXEC
ApplicationModules.Configuration.WriteConfigurationValue 'Web Framework','Server','MultiUseTokenEnabled',NULL,'true', 'GlobalSetting'
_____________________________________________________________________________________
Section 3 – Steps to Reproduce the Issue /Investigation/
How to check if Multi-Use Token is enabled
SELECT TOP (1000) [ItemType]
,[Item]
,[Key]
,[Value]
,[UserId]
,[Description]
FROM [ApplicationModules].[Configuration].[ConfigurationSettings]
where ItemType = 'Web Framework'
and Item = 'Server'
and [Key] = 'MultiUseTokenEnabled'
_____________________________________________________________________________________
Section 4 – Root Cause
Section 5 – Solution
How to enable the Multi-Use Token Functionality
UPDATE
[ApplicationModules].[Configuration].[ConfigurationSettings]
set Value = 'true' , [UserId] = 'GlobalSetting'
where ItemType = 'Web Framework' and Item = 'Server' and [Key] = 'MultiUseTokenEnabled'
After the authentication is enabled, use a web browser to navigate to:
https://<YourServerName>/Web/MUT.
EcoStruxure™ Energy Expert 3.0 Solution Guide
Energy Expert 3.0
Power Monitoring Expert 2020
_____________________________________________________________________________________
Section 2 – Issue
There is a mistake in the documentation EcoStruxure™ Energy Expert 3.0 Solution Guide on page 183. ( It has been observed that row is duplicated instead of updated)
The SQL script does not enable the multi-use token
EXEC
ApplicationModules.Configuration.WriteConfigurationValue 'Web Framework','Server','MultiUseTokenEnabled',NULL,'true', 'GlobalSetting'
_____________________________________________________________________________________
Section 3 – Steps to Reproduce the Issue /Investigation/
How to check if Multi-Use Token is enabled
- The functionality is by default disabled
- Must be set “True” in the ApplicationModules database, Configuration table (System stored procedures
SELECT TOP (1000) [ItemType]
,[Item]
,[Key]
,[Value]
,[UserId]
,[Description]
FROM [ApplicationModules].[Configuration].[ConfigurationSettings]
where ItemType = 'Web Framework'
and Item = 'Server'
and [Key] = 'MultiUseTokenEnabled'
_____________________________________________________________________________________
Section 4 – Root Cause
- Incorrect documentation
Section 5 – Solution
How to enable the Multi-Use Token Functionality
UPDATE
[ApplicationModules].[Configuration].[ConfigurationSettings]
set Value = 'true' , [UserId] = 'GlobalSetting'
where ItemType = 'Web Framework' and Item = 'Server' and [Key] = 'MultiUseTokenEnabled'
After the authentication is enabled, use a web browser to navigate to:
https://<YourServerName>/Web/MUT.
發佈於:施耐德電機Taiwan
探索更多
類別:
探索更多
類別: