Note: Implementing a new application in your IMDLRDH will erase your previous configuration.
To update the the application program of your IMDLRDH you need to :
To update the the application program of your IMDLRDH you need to :
- Have a formatted USB key
- Download the latest version of the application : https://www.se.com/ww/en/download/document/MFR2858700_Ver_2.0.0/
- Unzip the content and place the extracted files on the root of your USB Key
- Switch off the IMDLRDH
- Plug the USB Key in the USB port of the IMDLRDH
- Power on the IMDLRDH
- Wait for the program to be uploaded in the IMDLRDH
- Remove the USB key once the program is uploaded
發佈於: 施耐德電機Taiwan

