Netherlands 4.9.3 -In Ecodial is there any specific micrologic for MTZ2 'high performance' range of circuit breakers ?

NO,There is no specific micrologic for  ‘high performance’ range of circuit breaker It is only an electromechanical improvement in order to reach the performance 100kA, 1s (Icw at 1st - The rated short time withstand current at 1 second.)