搜尋常見問題
In Ecodial , Is there any relationship or coordination data available between the 'CIRCUIT BREAKER and MODULAR CONTACTORS?
In Ecodial, the relationship data or co ordination data is made available by considering only the "LED application" as follows:
MCB Rating (A) | Contactor iCT rating (A) |
10 | 16 |
16 | 25 |
20 | 40 |
32 | 63 |