搜尋常見問題
Is the low pressure cutoff option on a 9013 pressure switch adjustable?
Issue:
Adjustable Low Pressure Cut Off for 9013 Pressure Switches
Product Line:
Pressure, Vacuum, and Float Switches
Environment:
Type F—Pumptrol™ Water Pump Pressure
Switches
Resolution:
The low pressure cutoff remains fixed at 10psi below the low pressure cut in for the pressure switch. Although it is not independently adjustable, it will follow the low pressure set point. For this reason, it will not be effective if the cut in point is set below 10 psi.
Adjustable Low Pressure Cut Off for 9013 Pressure Switches
Product Line:
Pressure, Vacuum, and Float Switches
Environment:
Type F—Pumptrol™ Water Pump Pressure
Switches
Resolution:
The low pressure cutoff remains fixed at 10psi below the low pressure cut in for the pressure switch. Although it is not independently adjustable, it will follow the low pressure set point. For this reason, it will not be effective if the cut in point is set below 10 psi.
發佈於:施耐德電機Taiwan
探索更多
系列:
探索更多
系列: