Data Center Expert | How to view currently logged in users and historical logins
Answer
Issue
How to view currently logged in users and historical logins in Struxureware Data Center Expert

Product Line
StruxureWare Data Center Expert (DCE)
- Basic Appliance (AP9465)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)

Environment
StruxureWare Data Center Expert (all versions)
StruxureWare Central (all versions)
InfraStruXure Central (all versions)

Cause
Users may need to view who has logged in to the Struxureware Data Center Expert server for auditing purposes.

Resolution:
Log on to the web interface of Struxureware Data Center Expert and go to the "Event Log" tab. Choose "Security" from the category drop down menu. You can customize the the time range of events to display or choose from a predefined timeline.