{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
EPS UPSs or SSC with GUI that the touch point is off
Public

Issue:
EPS UPSs or SSC with GUI that the touch point is off

Product line:
All EPS UPSs or SSC with GUI

Environment:
All EPS UPSs or SSC with GUI

Cause:
The touch point is off on the GUI and needs to be calibrated to reset touch point.

Resolution:
How to calibrate the GUI:
1.            Click on Start->Settings->Control Panel->Stylus->Calibration->Recalibrate.
2.            Calibrate the five point accurately.
3.            Press ENTER if keyboard is connected else TAP on the screen, it will exit the calibration screen.
4.            Save registry from Start->Programs->ColibriTools->SaveReg.

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: