{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站

搜尋常見問題

How to solve the error message of E2558 multiple networks in macro section?

  1. Issue

Customer has concerted one PL7 application into Control Expert where it pops up “E2558 multiple networks in macro section (solution for SFC-Project-Setting 'Allow multiple token': move this network to chart section)”
How to solve this error message?
  1. Environment
E2558, SFCcontrol expert
  1. Resolution

The message is self-explainable as inside macro section, there only allows one network.
The problematic part is illustrated in the blue rectangle

Diagram  Description automatically generated
The fix solution is illustrated below
Diagram, schematic  Description automatically generated



施耐德電機Taiwan

探索更多
系列:
EcoStruxure Control Expert (Unity Pro)
探索更多
系列:
EcoStruxure Control Expert (Unity Pro)