Can TeSys Giga Relay be used along with TeSys D contactors (≤150A) ?
TeSys Giga overload relays can be used along with TeSys D contactors. However, they can’t be directly installed downstream to the contactor because the pitch between poles do not match. They can be individually installed with proper connection between them.
Note: There’s no coordination available for TeSys D contactors and LR9G relays
發佈於:施耐德電機Taiwan