{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
Can I connect the wireless panel server of PrismaSeT Active with a three-phase network without neutral?
The wiring kit can be powered without neutral. In this case the neutral cable must be removed from the gateway connector.

Please note that the voltage range of this three-phase electrical system is 3 x 230/400 (± 15%) V.

Just be aware that you will not be alerted in case of phase loss. Indeed, the LED will stay on because of the residual voltage but you will not be able to receive the alert on Facility Expert either.

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: