{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站

搜尋常見問題

What is the function of PLC input ON/OFF on TeSys Giga contactor ?

Normally the contactor operation is controlled by AC or DC control voltage input to A1-A2terminals. But in advanced version contactor, the contactor can be controlled by additional 24V DC PLC inputs to X1-X2-X3 terminals.

When the PLC switch is ON, the contactor function is controlled by PLC input.
When the PLC switch is OFF, the contactor is controlled by control voltage input to A1-A2.


image.png

The electrical schematic and function description are available on the installation guide DOCA0189EN and here is the link:TeSys Giga Series - Contactors and Electronic Overload Relays - Installation Guide User guide | Schneider Electric

施耐德電機Taiwan

探索更多
系列:
TeSys Giga contactors
探索更多
系列:
TeSys Giga contactors