Initial values from a converted Concept application does not get transferred to the PLC.
The reason this occurs is due to the checkbox for 'Initialize %MWi' not being selected in the CPU configuration.

To resolve the issue:
  • Open the CPU configuration window.
  • Select the checkbox 'Initialize %MWi'.
  • Rebuild the application.
  • Retest.