{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
Customer UPS report retrieval for Galaxy VL

Issue:
Customer UPS report retrieval for Galaxy VL

Product line:
Galaxy VL

Cause:
UPS report needed to troubleshoot UPS alarms properly prior to dispatch

Resolution:
See steps below on how to retrieve UPS report/logs.

1. Select Maintenance > UPS report.
2. Open the front door.
3. Insert your USB device in the USB port on the system-level controller.
4. Tap Export.
NOTE: Do not remove the USB device until the export process has
finished.
5. Send the UPS report to Schneider Electric customer support.

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: