{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
How to connect my Control Expert client to the server ?

Before launching Control Expert Topology Manager (TM) on the client side , please perform the following sequence :

1- Close TM on the server side

2- Open Server Configuration

3- Modify the Listening IP address in the Listening Connections tab : Either select the ethernet card with which you are communication with the client PC or type 0.0.0.0 to listen to all ethernet cards.

Server Configuration listenning IP address

4- Apply and close the tool.

5- Open TM on the client side and open User Preferences ;

6- Modify the Networkds And Servers tab, and modify the Control expert Server Address with the IP :

Here the IP address of my server is 192.168.189.1, the port to use is 19950.

User Preferences define IP address of TM server

7- Close and relaunch TM on the client side, and now you should be able to connect to the server.

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: