{}
搜尋常見問題
Machine Expert, need information about User Data Type limitations. Arrays and structures complexity and size.

Issue:

Need to know the limitations for Arrays and Structures complexity and size in EcoStruxure Machine Expert.

Product:

EcoStruxure Machine Expert software (all versions).

Answer:

EcoStruxure Machine Expert/Codesys does not limit the max array size or structure complexity.

The only limitation is the memory size of the controller.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: