{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站

搜尋常見問題

Can MDGF be combined with ZSI when Ground Fault Alarm is selected using breakers with micrologic 5.0P or H or 5.0x LSI?

No .When GF alarm is selected in a double or multiple ended substation and when tie or ties breakers are present, short time function must be self restrained and since GF protection is not available in the trip unit . ZSI option must be deselected.

施耐德電機Taiwan

探索更多
系列:
Power-Zone 4 Arc Resistant Low Voltage Switchgear with...Power-Zone 4 Low Voltage Switchgear with Masterpact NW and...Square D OEM QED2 SwitchboardsQED-2 Power-Style SwitchboardQED-S Power-Style Switchboard
探索更多
系列:
Power-Zone 4 Arc Resistant Low Voltage Switchgear with...Power-Zone 4 Low Voltage Switchgear with Masterpact NW and...Square D OEM QED2 SwitchboardsQED-2 Power-Style SwitchboardQED-S Power-Style Switchboard