{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站

搜尋常見問題

What are the Ground Fault Alarm pickup, dropout and time delay settings for Micrologic P and H trip units?

Issue:  Ground Fault alarm settings for Micrologic 5.0P, 6.0P, 5.0H, 6.0H trip units
Product Line: Circuit Breakers
Environment: Masterpact NW and NT, Powerpact P and R, Compact NS

Resolution:
100-400 amp sensors have a pickup and dropout range of .3xIn - 1xIn with a 1-10 second time delay
600-1200 amp sensors have a pickup and dropout range of .2xIn - 1xIn with a 1-10 second time delay
1250-6300 amp sensors have a pickup and dropout range of .1xIn - 1200 amps with a 1-10 second time delay

1 amp increments
0.1 second increments

施耐德電機Taiwan

探索更多
系列:
探索更多
系列: