For 115v input ATV12 drives, what should the UnS parameter be set at?

Issue:

For 115v input ATV12 drives, what should the UnS parameter be set at?

Product Line:

ATV12

Environment:

115v input

Cause:

n/a

Resolution:

If the Line voltage is less than the rated motor voltage, the rated motor voltage should

be set to the value of the line voltage, applied to the terminals.