搜尋常見問題
ECDSA 521 and Chrome
Issue:
NMC3 devices with an ECDSA 521 key cannot be launched to, over the web, through a Google Chrome web browser.
Product Line:
All NMC3 enabled devices
Cause:
The Google Chrome web browser is incompatible with the SSL certificates using ECDSA 521 encryption.
Resolution:
There are multiple options to resolve this issue.
NMC3 devices with an ECDSA 521 key cannot be launched to, over the web, through a Google Chrome web browser.
Product Line:
All NMC3 enabled devices
Cause:
The Google Chrome web browser is incompatible with the SSL certificates using ECDSA 521 encryption.
Resolution:
There are multiple options to resolve this issue.
- Switch to a different web browser (ex. Mozilla Firefox).
- Choose a different ECDSA encryption – both 256 and 384 are supported on the NMC3
- To change encryption, log into the device with SSH and run one of the following commands: ssl key -ecdsa 256 OR ssl key -ecdsa 384
- Use RSA instead of ECDSA. The NMC3 supports RSA 1024, 2048, and 4096.
- To use RSA encryption, the corresponding CLI commands are ssl key -rsa 1024 OR ssl key -rsa2048 OR ssl key -rsa 4096
發佈於:施耐德電機Taiwan
探索更多
系列:
探索更多
系列: