{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
Why does my Smart UPS Modular Ultra show "Unknown UPS internal error [3B7D-00A0]" on the display?
Issue:

After performing a UPS Firmware upgrade, removing and installing the Intelligence Modules, or when the UPS is booting up from a brains dead, you may see the display show "Unknown UPS internal error [3B7D-00A0]".


Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers


Resolution:

This specific message occurs when the Redundant Intelligence Module (RIM) is initializing after power up. In later versions of the NMC/Display firmware, the messaging is changed to "RIM initializing, Do not remove MIM".  Please upgrade the NMC/Display firmware to SUCAN 2.5.1.3 to see update messaging.   You can upgrade the firmware by following this FAQ: https://www.apc.com/us/en/faqs/FAQ000261841/

施耐德電機Taiwan

探索更多
產品:
可能有幫助的文章
探索更多
產品: