{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站

搜尋常見問題

ION9000 Data Not Showing on Connected Panel Server

Issue: ION9000 is serially connected to Panel Server. Registers can be read on the panel server and through Modscan but data is not populating on the panel server webpage.

Product Line:

ION9000
EcoStruxure  Panel Server - Advanced
EcoStruxure  Panel Server - Universal

Environment:

Panel Server Webpage

Cause: The Panel Server does not have a native device file for the ION9000.

Resolution:

A custom device file will have to be created in order to see data. This can be done in EcoStruxure Power Commission. Reference:

Custom Models for Downstream Modbus Devices (Universal and Advanced Models)

施耐德電機Taiwan

附件

Panel Server - User Guide - 2022.pdfPanel Server - User Guide - 2022.pdf [31.27 MB]
探索更多
系列:
EcoStruxure Panel ServerPowerLogic™ ION9000
探索更多
系列:
EcoStruxure Panel ServerPowerLogic™ ION9000