How do you set up the damper control on the enclosed S-Flex ATV212 Drive?
Issue:
Setting up the damper control on the enclosed S-Flex ATV212 Drive

Product Line:
S-Flex ATV212 with bypass

Environment:
All

Cause:
Wants to wire in a damper control circuit to allow the damper to open before running the motor thru the drive.

Resolution:
Step #1 Customer commands the drive to run by closing terminals (5-6) auto start. (Drive will not start at this time or until damper is opened)

Step #2 Closing the auto start terminals  (5-6) will energize the RPR relay which will close user contacts (19-20) to start damper solenoid coil.

Step #3 Damper solenoid will start to open damper.

Step# 4 Once the damper is open the customer will need to provide a end of damper feedback limit switch.

Step #5 Remove the jumper from terminals (3-4) and wire your end of damper feedback dry NO contact to terminal (3-4).

Please note that this damper function will only work in the remote control mode by closing contacts (5-6) and not the local mode run button on the face of the drive.

Schneider Electric Україна

Інформація була корисною?
How do you set up the damper control on the enclosed S-Flex ATV212 Drive?
Issue:
Setting up the damper control on the enclosed S-Flex ATV212 Drive

Product Line:
S-Flex ATV212 with bypass 

Environment:
All 

Cause:
Wants to wire in a damper control circuit to allow the damper to open before running the motor thru the drive. 

Resolution:
Step #1 Customer commands the drive to run by closing terminals (5-6) auto start. (Drive will not start at this time or until damper is opened)

Step #2 Closing the auto start terminals  (5-6) will energize the RPR relay which will close user contacts (19-20) to start damper solenoid coil.

Step #3 Damper solenoid will start to open damper.

Step# 4 Once the damper is open the customer will need to provide a end of damper feedback limit switch. 

Step #5 Remove the jumper from terminals (3-4) and wire your end of damper feedback dry NO contact to terminal (3-4).

Please note that this damper function will only work in the remote control mode by closing contacts (5-6) and not the local mode run button on the face of the drive. 

Schneider Electric Україна

Інформація була корисною?
Досліджуйте більше
Продукт:
Серія:
Досліджуйте більше
Продукт:
Серія:
Досліджуйте більше
Продукт:
Серія:
Досліджуйте більше
Продукт:
Серія:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.