{}

Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.

Пошук серед найпопулярніших питань

Getting premature schedule manufacturer maintenance alarm on Masterpact MTZ Micrologic X control unit

Issue:
Why am I getting a scheduled maintenance alarm when  the breaker is brand new and recently placed into service?
Sched. Manufact. maintenance within 3 months  Id: 0x1482

Product Line: Circuit Breakers

Environment: Masterpact MTZ with Micrologic X  control unit

Resolution:
The commissioning date within the control unit may have been left blank.  Use EcoStruxure Power Commision (EPC) commissioning software to correctly fill in the commissioning date.  See attached screen shot, to locate commissioning date in EPC.

Schneider Electric Україна

Вкладення

Commissioning Date in EPC.jpgCommissioning Date in EPC.jpg [27.21 KB]
MTZ Schedule manufacturer maintenance within 3 months on display Id 0x1482.JPG.jpgMTZ Schedule manufacturer maintenance within 3 months on display Id 0x1482.JPG.jpg [61.76 KB]
Досліджуйте більше
Серія:
Досліджуйте більше
Серія: