Issue:
DC injection braking setup on the ATV212 drives.
Product Line:
ATV212
Environment:
DC Injection braking
Cause:
N/A
Resolution:
Program the following:
F250 = DC braking starting frequency, set to a value > 0
F251 = DC braking current level
F252 = DC braking time
Caution: Prolonged periods of DC injection can damage the motor.
DC injection braking setup on the ATV212 drives.
Product Line:
ATV212
Environment:
DC Injection braking
Cause:
N/A
Resolution:
Program the following:
F250 = DC braking starting frequency, set to a value > 0
F251 = DC braking current level
F252 = DC braking time
Caution: Prolonged periods of DC injection can damage the motor.